SMOLPy also models Modbus TCP — a request/response protocol, unlike MQTT's fire-and-forget publish/subscribe. Because Modbus TCP already wraps its PDU in a standard Ethernet/IP/TCP frame (no serial bus, no gateway required), a ModbusSlave is a first-class network node wired into the same switch fabric as any Adapter.

What is modelled

  • The master is a regular Adapter — it calls polls() to periodically send Read Holding Registers (FC 03) requests toward a ModbusSlave.
  • Each slave is addressed by its own unit_id (1–247); it replies only to requests matching its unit_id and ignores everything else. Multiple sensors can share one switch, each polled independently by the same master.
  • Every poll is a request/response round trip — both frames traverse the network and contend for bandwidth, unlike MQTT where only the publisher-to-broker leg carries the payload.
  • modbus_latency measures poll round-trip time (RTT): the time from when the master sends a request to when the matching response arrives back. This is the key metric for judging whether a polling interval is achievable on a given network.

Frame size formula

request_size  = 65 bytes                                  (constant — Ethernet/IP/TCP + MBAP + FC + address + quantity)
response_size = 62 + 2 × register_count bytes              (grows with the number of registers read)

Dashboard

ModbusSlave nodes appear as coral red circles in the topology panel — see Dashboard.

See example_modbus.py for a full working scenario — a PLC polling three field sensors while sharing its uplink with regular Ethernet traffic — or Examples for the write-up.